ALSTOM UT129-C1 Full Technical Specification
Basic Product Information
Brand: ALSTOM
Model: UT129-C1 (Alias: UT129C-1)
Official Order Part Number: C0201450
Full Product Name: CE2000 Safety Control Processing Unit
Country of Origin: France
Customs HS Code: 8538900000 (Parts for industrial automation control equipment)
Overall Dimension: 265 mm (W) × 36 mm (H) × 265 mm (D)
Net Weight: 0.60 kg
Mounting Method: Standard rack plug-in installation for control cabinet
Protection Class: IP20 (Indoor cabinet installation only)
Standard Firmware Version: VM07.02

Power Input Parameters
1. Rated Supply Voltage: 24 V DC, tolerance range -15% ~ +30%
2. Working Input Current: Max 280 mA
3. Rated Power Consumption: ≤ 6.7 W
4. Built-in protection: Reverse polarity, overvoltage, short-circuit and surge suppression
5. Bus Communication Input Interface: WorldFIP copper bus, communication rate 1 Mbps; cannot be mixed with UT150-1 module on the same network segment
Signal Input Specifications
1. Local I/O Expansion Input: Supports signal access from 16 matched digital/analog I/O modules
2. Digital Input Compatibility: 24 V DC NPN/PNP field switch signals, with line break diagnosis function
3. Analog Input Compatibility: Standard 4–20 mA analog measuring signals
4. Bus Data Input: Real-time safety logic commands and parameter data transmitted from upper CE2000 main controller via WorldFIP bus
5. Hardware Diagnostics Input: Internal self-test circuit for power supply, bus channel and processor status
Signal Output Specifications
1. Field I/O Control Output: Sending logic control instructions to connected 16-channel I/O modules to drive on-site actuators
2. Bus Communication Output: Upload real-time operating data, fault alarms and field signal values to upper host controller through WorldFIP bus
3. Fault Alarm Output: On-board LED indicator output for module abnormal, bus disconnection, power failure and channel failure
4. Logic Execution Output: Independent closed-loop safety interlock output for boiler protection and emergency shutdown logic
Environmental & Performance Parameters
1. Operating Ambient Temperature: -20 ℃ ~ +60 ℃
2. Storage Temperature: -40 ℃ ~ +70 ℃
3. Certification: CE industrial safety certification, thermal power boiler safety application certification
4. Onboard Memory: 32 MB system storage
5. Supported Protocols: WorldFIP dedicated industrial safety bus
6. Shock & Vibration Resistance: Compliant with IEC 60068-2-6 industrial standard





There are no reviews yet.